FJT Power Logo
FJT POWER
Generator Solution Supplier
Zoom In
CUMMINS INDUSTRIAL

1250kVA Cummins Power Generator C1400D5

100% Factory Tested
Global Warranty
ISO 9001 Certified
Genset Model
C1400D5
Prime Power(kVA)
1250
Engine
KTA50-G3
Alternator
N/A
Controller
DSE7420 MKII recommended
Ideal Power Solution For:
Manufacturing
Data Centers
Mining & Construction
Healthcare
Commercial

Technical Data Sheet

Generator Set Specifications

Item Specification
Genset model C1400D5
Prime power 1250kVA / 1000kW
Standby power 1400kVA / 1120kW
Data center continuous power 1250kVA / 1000kW
Rated voltage 400/230V, configurable within 380-440V project requirements
Frequency 50Hz
Rated speed 1500rpm
Phase 3 phase, 4 wire
Power factor 0.8 lagging
Duty Prime power
Application Industrial generator set
Engine brand Cummins
Engine model KTA50-G3
Fuel type Diesel
Controller model DSE7420 MKII recommended DeepSea controller
Fuel consumption at full prime load 261 L/h
Fuel consumption at full standby load 293 L/h
Calculated full-prime fuel rate About 0.261 L/kWh at 1000kW
Open dimensions 5143 x 2000 x 2518 mm
Open dry weight 9913 kg
Open wet weight 10069 kg
Silent / ISO container dimensions 12192 x 2438 x 2896 mm, 3233 mm with exhaust stack
Silent / ISO container dry weight 17419 kg
Silent / ISO container wet weight 17575 kg
Silent noise level Based on Cummins sound data sheet MSP-2040 for the C1400D5 enclosed configuration

Engine Specifications

Item Specification
Engine brand Cummins
Engine model KTA50-G3
Engine type Cast iron, 4-cycle, 60-degree Vee diesel engine
Cylinders 16V
Displacement 50.3 L
Bore x stroke 159 mm x 159 mm
Compression ratio 13.9:1
Rated speed 1500rpm
Aspiration Turbocharged and after-cooled
Fuel system Direct injection diesel fuel system
Cooling system Set-mounted radiator cooling, 40C standard with 50C and 55C options
Governor Electronic governor
Starting system 24V DC electric start
Gross engine power output 1075kWm prime / 1251kWm standby
Lubricating oil system capacity 152 L
Coolant capacity with radiator 424 L
Overspeed limit 1725rpm +/- 50
Fuel consumption 261 L/h at full prime load; 293 L/h at full standby load

Alternator Specifications

Item Specification
Alternator brand Cummins / Stamford equivalent
Alternator model PI734B low-voltage alternator, with S7L1D-C4 and S6L1D-H4 options
Output rating Matched for 1250kVA / 1000kW prime and 1400kVA / 1120kW standby
Rated voltage 400/230V
Voltage range 380-440V
Frequency 50Hz
Phase 3 phase, 4 wire
Connection Wye, 3-phase
Power factor 0.8 lagging
Temperature rise 150/125 C standby / prime configuration available
Poles 4 pole
Insulation class Class H
Protection class IP23
AVR Automatic voltage regulator
Excitation system Brushless, self-excited with PMG support
Bearing type Two bearing
Voltage regulation +/- 1.0% typical

Before confirming this configuration