FJT Power Logo
FJT POWER
Generator Solution Supplier
Zoom In
CUMMINS INDUSTRIAL

200kW 250kkVA Cummins Generator Set QSL8.9-G34

100% Factory Tested
Global Warranty
ISO 9001 Certified
Genset Model
TPD275C5-3
Prime Power(kVA)
250
Engine
QSL8.9-G34
Alternator
N/A
Controller
DSE7320 MKII/DSE8610 MKII
Ideal Power Solution For:
Manufacturing
Data Centers
Mining & Construction
Healthcare
Commercial

Technical Data Sheet

Generator Set Specifications

Specification Technical Data
Product Name 200kW 250kVA Cummins Generator Set QSL8.9-G34
Genset Model C250D5 / 200kW Cummins Land Type Diesel Generator
Prime Power (PRP) 200 kW / 250 kVA
Standby Power (ESP) 220 kW / 275 kVA
Engine Model Cummins QSL8.9-G34
Recommended Alternator Stamford UCDI274K / S4L1D-C41
Rated Voltage 400V / 230V (Customizable to 380V, 415V, 440V, 480V)
Rated Frequency 50Hz
Rated Speed 1500 RPM
Rated Current 361 Amps at 400V, 3-phase
Power Factor 0.8 (Lagging)
Phase & Connection 3 Phase, 4 Wire (Y-type connection)
Cooling Method Closed water-cooled radiator system
Starting System 24V DC electric start
Control System Deep Sea DSE7320 MKII
Voltage Regulation AVR automatic voltage regulation, ±1.0%

Engine Specifications

Specification Technical Data
Engine Manufacturer Cummins
Engine Model QSL8.9-G34
Engine Type 6-cylinder in-line, 4-stroke diesel engine
Aspiration Turbocharged and Charge Air Cooled
Displacement 8.9 Liters
Bore × Stroke 114 mm × 145 mm
Compression Ratio 16.6 : 1
Rated Speed 1500 RPM
Gross Engine Output Approx. 225 kWm (Prime Power)
Fuel System High-Pressure Common Rail (HPCR)
Governor Type Electronic governor (ECM)
Cooling System Radiator water-cooled system
Lube Oil Capacity 34.0 Liters
Coolant Capacity Approx. 41 Liters (including radiator)
Fuel Consumption (100% Load) 52.0 Liters/hour
Fuel Consumption (75% Load) 39.0 Liters/hour
Fuel Consumption (50% Load) 27.0 Liters/hour

Alternator Specifications

Specification Technical Data
Alternator Brand Stamford
Recommended Model UCDI274K (or equivalent S4L1D-C41)
Rated Output 250 kVA / 200 kW
Rated Voltage 400V / 230V
Rated Frequency 50Hz
Power Factor 0.8 lagging
Excitation System Brushless, self-excited (PMG optional)
AVR Model AS440 / MX341
Voltage Regulation ±1.0%
Insulation Class Class H
Protection Grade IP23
Winding Pitch 2/3 pitch
Bearing Type Single bearing

Before confirming this configuration

Confirm the required duty, electrical supply, installation interfaces and scope of supply when requesting this product. Unknown requirements can be discussed in the inquiry.

More languages · automatic translation