360kVA Cummins Power Generator C400D5
Power: 288kW / 360kVA
Engine: QSG12-G3
Frequency: 50Hz
View Specs
| Specification | Technical Data |
|---|---|
| Product Name | 280kW 350kVA Cummins Generator Set NTA855-G2 |
| Genset Model | TPD350C5-3 Land Type Cummins Diesel Generator Set |
| Prime Power | 280 kW / 350 kVA |
| Standby Power | 308 kW / 385 kVA |
| Engine Model | Cummins NTA855-G2 |
| Recommended Alternator | Stamford HCI444E / HCI444FS |
| Rated Voltage | 400V / 230V |
| Voltage Options | 380V, 415V, 440V, 480V available upon request |
| Rated Frequency | 50Hz |
| Rated Speed | 1500 RPM |
| Rated Current | 505.2 A at 400V, 3-phase |
| Power Factor | 0.8 lagging |
| Phase & Wire | 3 Phase, 4 Wire |
| Connection Type | Star / Y connection |
| Cooling Method | Closed water-cooled radiator system |
| Starting System | 24V DC electric start |
| Control System | Deep Sea DSE7320 MKII digital controller |
| Governor Type | Mechanical governor, electronic governor optional |
| Voltage Regulation | AVR automatic voltage regulation, ±1.0% |
| Fuel Type | Diesel |
| Fuel Tank | Base fuel tank optional for silent type |
| Application | Industrial power supply, factory backup power, construction site power, data center standby power, commercial building emergency power |
| Open Type Dimension | 3000 × 1100 × 1850 mm |
| Open Type Weight | 2760 kg |
| Silent Type Dimension | 4000 × 1400 × 2150 mm |
| Silent Type Weight | 4400 kg |
| Specification | Technical Data |
|---|---|
| Engine Manufacturer | Cummins |
| Engine Model | NTA855-G2 |
| Engine Type | 6-cylinder in-line, 4-stroke diesel engine |
| Aspiration | Turbocharged and aftercooled |
| Displacement | 14.0 L |
| Bore × Stroke | 140 mm × 152 mm |
| Compression Ratio | 14.0 : 1 |
| Rated Speed | 1500 RPM |
| Rated Engine Output | Approx. 317 kWm for generator drive application |
| Fuel System | Cummins PT fuel system |
| Governor Type | Mechanical governor / electronic governor optional |
| Cooling System | Radiator water-cooled system |
| Starting Voltage | 24V DC |
| Battery Charging Alternator | 24V DC charging alternator |
| Lube Oil Capacity | Approx. 38.6 L |
| Coolant Capacity | Approx. 60 L, depending on radiator configuration |
| Fuel Consumption at 100% Load | Approx. 72–76 L/h |
| Fuel Consumption at 75% Load | Approx. 55–58 L/h |
| Fuel Consumption at 50% Load | Approx. 38–42 L/h |
| Air Intake Flow | Approx. 520 L/s |
| Exhaust Gas Flow | Approx. 980 L/s |
| Exhaust Gas Temperature | Approx. 500–540°C |
| Engine Feature | Heavy-duty Cummins NTA855 series engine with strong torque output, stable performance, and easy maintenance |
| Specification | Technical Data |
|---|---|
| Alternator Brand | Stamford |
| Recommended Alternator Model | Stamford HCI444E / HCI444FS |
| Rated Output | 350 kVA / 280 kW |
| Rated Voltage | 400V / 230V, customizable |
| Rated Frequency | 50Hz |
| Rated Speed | 1500 RPM |
| Power Factor | 0.8 lagging |
| Phase | 3 Phase |
| Excitation System | Brushless, self-excited |
| PMG Option | PMG available for better motor-starting performance |
| AVR Model | SX460 / AS440 / MX341 depending on configuration |
| Voltage Regulation | ±1.0% standard, ±0.5% optional |
| Insulation Class | Class H |
| Protection Grade | IP23 standard |
| Optional Protection Grade | IP44 / IP55 available upon request |
| Winding Pitch | 2/3 pitch for harmonic reduction |
| Bearing Type | Single bearing, double bearing optional |
| Cooling Method | Self-ventilated |
| Waveform Distortion | Low waveform distortion for stable industrial power output |
| Application | Suitable for 280kW Cummins generator set, 350kVA industrial diesel generator, and heavy-duty standby power systems |
Confirm the required duty, electrical supply, installation interfaces and scope of supply when requesting this product. Unknown requirements can be discussed in the inquiry.